Choose by system, not by habit: new Split/commercial = R-32 · VRF/legacy = R-410A · chillers = R-134a/R-513A · cold room/ice plant = R-404A→move to R-448A/R-449A · new automotive = R-1234yf · ULT/freeze-dryer = R-508B/R-23. Hard rule: never top-up a zeotropic blend — recover and recharge fully by weight; HFC/HFO retrofits require POE oil.
Every job site brings the HVAC/R contractor the same questions: "Which refrigerant does this system need? Can I use a substitute? Where do I source it in time?" A single wrong choice can mean a burned-out compressor, a repeat leak, an unpaid invoice, or a free return trip to fix the job.
This is a field guide for contractors and service teams — a complete set of refrigerant-selection tables organized by the real system types you meet in Thailand, plus drop-in/retrofit options for the R-22 and R-404A that are being phased out, the compressor oil you must change alongside them, and how to source cylinders so they're in stock, on time, at fleet pricing.
This is the "pick-it-right-on-site" overview — each section links to a dedicated deep-dive article if you need to go further on a specific refrigerant.
Three rules before you choose
- Choose by system and nameplate, not by habit — each unit is engineered around a specific refrigerant's pressure and oil. Always read the nameplate on the condensing unit.
- A leaked blend must be fully recharged by weight, never topped up — glide makes the composition drift.
- Changing refrigerant always means thinking about compressor oil — HFC/HFO require POE, not mineral oil.
Master table: refrigerant by system type
| System | Primary (new equipment) | Legacy / still seen on site | Safety class (ASHRAE 34) | Deep dive |
|---|---|---|---|---|
| Residential / Split / wall / ceiling-floor | R-32 | R-410A, R-22 (very old) | R-32 = A2L · R-410A = A1 | R-32 vs R-410A |
| Light-commercial / Package / Rooftop | R-32, R-410A | R-22, R-407C | A2L / A1 | R-22 → R-32/R-454B |
| VRF / VRV | R-410A (some 2024+ brands R-32 / R-454B) | R-410A | A1 / A2L | VRF/VRV vs Chiller |
| Chiller — Screw / Scroll / Recip (positive displacement) | R-134a, R-513A (low-GWP HFO) | R-22, R-407C | A1 | Glycol Chiller vs DX |
| Chiller — Centrifugal (low-pressure) | R-1233zd, R-514A, R-1234ze | R-123 (HCFC, phase-out) | A1 / B1 | HFO alternatives |
| Cold Room — Medium Temp (MT, 0 to +10°C) | R-448A / R-449A (moving off R-404A) | R-404A, R-507, R-22, R-407F | A1 | Cold Room / Blast Freezer |
| Freezer — Low Temp (LT, -18 to -25°C) | R-448A / R-449A, R-404A | R-404A, R-507, R-22 | A1 | Cold Room / Blast Freezer |
| Ice plant / Industrial refrigeration | R-404A → R-448A/R-449A, R-717 (NH₃) for large plants | R-404A, R-22, R-717 | A1 · NH₃ = B2L | Natural Refrigerants |
| Small commercial plug-in coolers/freezers | R-290 (propane), R-600a | R-134a, R-404A | A3 (flammable — sealed units) | Natural Refrigerants |
| Automotive (MAC) | R-1234yf (new vehicles) | R-134a | A2L / A1 | R-134a vs R-1234yf |
| ULT / freeze-dryer / cascade (-40 to -80°C) | R-508B, R-23, ISCEON MO89 | R-13B1, R-503, R-23 | A1 | ULT/VLT retrofit · R-744 vs R-23 |
| Supermarket / commercial CO₂ | R-744 (CO₂) transcritical | R-404A | A1 | R-744 vs R-23 |
Always read the nameplate first — this table gets you to the right family, but the actual unit may specify a particular grade (e.g. some 2024+ VRF brands have moved to R-454B).
Retrofit / drop-in table — when the original is scarce or expensive
R-22 and R-404A are where contractors hit "expensive/out-of-stock" most. These are the substitutes actually used in service work:
| Original | Working substitute | For | Oil required | Key note |
|---|---|---|---|---|
| R-22 (comfort) | R-407C | A/C, comfort chillers | POE (flush out MO) | high glide — liquid charge only |
| R-22 (fast drop-in) | R-422D, R-438A (MO99) | A/C, MT refrigeration | tolerates residual MO | slight capacity loss |
| R-22 (MT/LT refrigeration) | R-407F, R-407A | cold rooms | POE | better capacity than R-407C in refrigeration |
| R-404A / R-507 | R-448A (N40), R-449A (XP40) | cold room / ice plant MT-LT | POE | ~65% lower GWP — the new standard for refrigeration |
| R-410A | R-32 (new units), R-454B (XL41) | A/C, VRF (compatible units) | POE | ❌ don't retrofit existing R-410A to R-32 in units not designed for it (pressure/A2L) |
| R-134a | R-513A (XP10), R-450A | chillers / medium-temp | POE | A1 non-flammable — easy chiller retrofit |
| R-123 (centrifugal) | R-1233zd, R-514A | low-pressure centrifugal chiller | per manufacturer | major job — assess with the OEM |
See a deep comparison of the low-GWP HFO options (R-449A / R-454B / R-513A) in the HFO comparison article, and the R-22 transition path in the R-22 phase-out guide.
The compressor-oil trap contractors fall into
This is the single most common reason a retrofit ends in a dead compressor:
- Legacy R-22 uses Mineral Oil (MO) or Alkylbenzene (AB) — the oil mixes with R-22 and returns to the compressor normally.
- All HFC/HFO (R-32, R-410A, R-404A, R-448A, R-134a, R-513A) require POE (Polyol Ester) — MO does not mix with HFC, so the oil stays trapped in the system and never returns → the compressor runs oil-starved and fails within 6-12 months.
- POE is strongly hygroscopic — it absorbs moisture fast, so you can't leave the can open; pull a deep vacuum (below 500 microns) and change the filter-drier every time.
- Some drop-ins (R-422D, R-438A) tolerate residual MO, so an incomplete oil change still works — but the cleanest retrofit flushes and converts to POE.
Charge it right — by weight, not by pressure alone
For blends with glide, the correct charging procedure is:
- Recover the old charge fully — never vent to atmosphere (illegal + high GWP).
- Fix the leak and evacuate deep enough (below 500 microns for POE work).
- Charge as liquid from the cylinder by the specified weight — not as vapour drawn off the top, which gives a skewed composition.
- Estimate the charge / cooling load with the refrigerant / cooling-load calculator, then confirm against the actual unit spec.
Systems with a history of repeat leaks should have a gas detector per ASHRAE 15 / EN 378 / ISO 5149, especially in machine rooms and enclosed spaces.
Safety and law contractors must know (in brief)
- R-32 and A2L refrigerants are mildly flammable — work in well-ventilated areas, keep ignition sources/flames away during charging, and use appropriate tools (see the R-32 A2L handling guide).
- R-717 (ammonia) is B2L — toxic, needs dedicated ventilation/detection — large systems only.
- HFC refrigerants are classed as hazardous substances under Thai law — suppliers must be licensed and ship with full SDS (Safety Data Sheet), UN Number labelling, and Hazard Diamond.
- Never vent refrigerant — recover and send to a licensed reclaim facility (see refrigerant reclaim in Thailand).
For contractors: how to source so cylinders are ready, on time, at fleet pricing
The biggest profit leak for contractors isn't "picking the wrong grade" — it's "out of stock, late delivery, swinging prices." Fix it by planning purchasing with a supplier who carries every grade:
| On-site problem | Purchasing fix |
|---|---|
| Refilling on nearly every job, but prices swing monthly | Order ahead as a fleet → lock pricing for the year, cut volatility |
| Rush job, but the grade you need is out of stock | Use a supplier with all grades in stock — no chasing multiple shops |
| Working under a company name, need tax invoice + SDS | Buy from a supplier who issues tax invoice + SDS + CoA every time |
| Retail pricing erodes margin | Order by the cylinder/case → contractor/fleet pricing |
Sahawatthanakit (1988) Co., Ltd. supplies the full range of refrigerants — R-32, R-410A, R-22, R-134a, R-404A, R-407C, R-448A/R-449A, R-507 and more — built for contractor and service-fleet teams:
- ✅ In stock, all grades — no running between shops
- ✅ Fleet pricing + lock pricing ahead for the year
- ✅ SDS + tax invoice + CoA on every order
- ✅ Delivery nationwide, express in Bangkok / Nonthaburi / Pathum Thani
Order and request a quote (contractor pricing)
Tell us the grades + your typical volume + delivery location and get a quote within 24 hours:
- 📞 Call: 02-096-2118 / 061-541-6939 (Khun Nawin)
- 💬 LINE: @406rrgvm
- 📧 Email: info@sahawatthanakit1988.com
- 🌐 Request a refrigerant quote (fleet pricing) →
- ⏰ Mon–Sat 08:30–17:30 | 🚚 nationwide delivery
Contractor tip: include your rough annual volume and we'll set steady fleet pricing and delivery cycles for the whole year — so you're never chasing refrigerant during a rush job.
Get this guide as a reference brief (PDF)
Summary + full section list + standards cited, Saha-branded for your memo/RFQ — emailed to you too.
Questions after reading? Talk to our engineers
Tell us what you need — our engineers help you spec it right, with a real quote. No charge.
Need help with this in your facility?
Our team handles full procurement and installation for the topics covered in this article. Free quote within 2 hours.
Frequently Asked Questions
1Which refrigerant should a new unit use?
+
2What replaces R-22, and can I just top it up?
+
3Why can't I top-up a blend (R-410A, R-404A) after a leak?
+
4Do I have to change compressor oil when retrofitting from R-22 or R-404A?
+
5What's the minimum order for cylinders at contractor/fleet pricing?
+
Comparison tables related to this article
Related content
VRF/VRV vs Chilled-Water Chiller: Choosing Factory/Office/Cleanroom HVAC — Load, Efficiency, and EN 378 Refrigerant-Charge Limits for Thailand
Industrial HVAC buyer's guide: compare VRF/VRV (refrigerant-to-room) vs chilled-water chiller (AHU/FCU) → calculate cooling load → IEER/IPLV efficiency → R-32 A2L charge limits per EN 378 / ISO 5149 → contractor checklist + cleanroom considerations + Thai ambient +38°C de-rating for factories and offices.
Industrial Cold Room / Cold Storage: Chiller vs Freezer vs Blast Freezer + Refrigerant Selection + Cooling Load Calculation + EN 378/GDP Standards for Thai Food, Pharma & Logistics Plants
Buyer's guide to industrial cold storage: separate chiller (+2 to +8°C) / freezer (−18 to −25°C) / blast freezer → calculate real cooling load before sizing → compare refrigerants R-449A/R-448A/R-290/R-744/NH3 → choose PIR panel thickness → contractor checklist + EN 378/ISO 5149/GDP/HACCP standards for plants in Thailand.
R-22 → R-32 / R-454B Chiller Conversion Playbook — Get Ready Before Thailand's 2030 Phase-out
Practical guide to converting R-22 (HCFC) industrial chillers to R-32 / R-454B (HFO) ahead of the Kigali Amendment + DIW Thailand 2030 phase-out — costs, which machines can be converted, TXV/EXV comparison table, and A2L safety requirements.
R32 / R410a Refrigerant Prices and Suppliers in Thailand 2026 — Buying Guide for Technicians and Factories
Compare R32 and R410a refrigerant prices in Thailand for 2026 with a GWP table, purchasing methods, minimum order quantities, and certified suppliers, for air-conditioning technicians and industrial plants
