Refrigerants compared

R-32 vs R-410A vs R-22Which one fits your job?

The three most-used refrigerants in Thailand — full specs + phase-out timeline + retrofit options + real 2026 pricing

In short — which to choose?

Depends on the application + age of the equipment — pick by the rows below

Default choice 2024+

R-32

  • GWP 675 — lowest among common HFCs (R-410A is 3× higher)
  • 5-8% lower energy consumption vs R-410A (electricity saver)
  • New residential + light commercial units have all moved to R-32
  • A2L — mildly flammable — technicians need ASHRAE 34 / EN 378 certification
Best for

New residential / SME AC 2024+, heat pump systems, low-GWP regulation in every country

Phase-down on schedule

R-410A

  • Legacy HFC — nearly every commercial system from 2010-2024 uses it
  • A1 non-flammable — any technician can handle it
  • Kigali Amendment: 80% consumption cut by 2036
  • Replacement (low-GWP): Opteon XL55 / Solstice N41 (R-454B)
Best for

VRF, chillers, large commercial AC not yet retrofitted

Phase-out — discontinued

R-22

  • ODP 0.055 — depletes the ozone layer (Montreal Protocol)
  • No new imports into Thailand from 2030 — recycled stock only after that
  • Price keeps rising — supply is tight
  • Drop-in: R-407C, Opteon XL41 (R-454A) for retrofit
Best for

Repairs of old units not yet retrofitted only — never for new systems

12-point comparison table

ItemR-32R-410AR-22
TypeHFC (A2L mildly flammable)HFC blend (A1 non-flammable)HCFC (A1 non-flammable)
GWP (100-year)6752,0881,810
ODP (ozone depletion)000.055 (non-zero!)
Operating pressure~10% higher than R-410AHighLow-medium
Cooling capacity (single AC)+10% vs R-410Abaseline−5% vs R-410A
Energy efficiency (COP)+5-8% vs R-410Abaseline−10% vs R-410A
Thailand phase-out timelineAllowed — the new standardPhase-down — Kigali 2024-2036No new imports from 2030 (Montreal)
Price (13.6 kg cylinder)quote-only — ask for a live pricequote-only — higher than R-32quote-only — tightening with the phase-out
Charge per system~30% less (single component)baseline (zeotropic blend)Close to R-410A
Retrofit from R-22?✗ Needs a new compressor + oil✗ Needs a new expansion valve + oildrop-in: R-407C / Opteon XL41
Compressor oilPOEPOEMineral / Alkylbenzene
Best useNew residential + light commercial AC, 2024+Existing commercial systems + VRF / chillersRetrofit of very old units only

Caution

A2L (R-32) requires a certified technician — with leak detection + ventilation. Use in malls/hospitals must comply with ASHRAE 15 + EN 378

Can't decide? Our engineers pick by system size

Tell us the BTU + unit type (split/VRF/chiller) → we calculate + recommend the right refrigerant + a free quotation

Related comparisons

Decide with confidence — compare from several angles

Read the related comparison tables — full specs, real prices, and a recommendation for each use.

FAQ

Common Questions

Q1.When will R-22 phase out in Thailand?+
Per Montreal Protocol + Kigali Amendment 2016 (Thailand signed 2019) — R-22 import banned from 2030, existing stock sellable through 2040. Existing systems can still be recharged but at rising cost. Recommended: retrofit to R-32 within 3-5 years.
Q2.Can I retrofit R-22 to R-32?+
Direct drop-in not recommended. R-32 uses POE oil (R-22 uses mineral oil) and runs ~60% higher pressure. Requires compressor + expansion valve + copper line resize. Only cost-effective for new systems — for aging R-22 units, replace at end-of-life rather than retrofit.
Q3.If I don't want to change the compressor, is there a drop-in R-22 replacement?+
Yes — R417a is an A1 (non-flammable) drop-in for R-22 that works on the existing system without swapping the compressor or valves, a good bridge when you're not ready to invest in a new R-32 unit (trade-off: slightly lower COP than original R-22). It's a made-to-order, quote-only item. For legacy low-pressure centrifugal chillers on R-11/R-123, we can also supply R123.
Q4.Is R-32 (A2L) flammable — is it dangerous?+
R-32 is classified A2L (mildly flammable) per ASHRAE 34 + ISO 817. Hard to ignite — LFL 14% in air, ignition energy 30× higher than propane. IEC 60335-2-40 caps max charge per room. Safe with adequate ventilation and no ignition sources >750°C nearby.
Q5.What are the GWP values?+
Global Warming Potential (100-year, IPCC AR4): • R-22 = 1,810 (HCFC, phasing out) • R-410A = 2,088 (high-GWP HFC blend) • R-32 = 675 (low-GWP HFC) Kigali Amendment requires Thailand HFC consumption -10% by 2029, -50% by 2045.
Q6.Is R-410A getting hard to find — has price risen?+
Still available — Daikin/Carrier/Mitsubishi continue to sell in Thailand. But price rose 30-50% during 2024-2025 due to HFC phase-down. Most new AC units since 2023 use R-32 instead. Existing R-410A systems can still be serviced normally.