Sahawatthanakit (1988) Co., Ltd.
SAHAWATTHANAKIT(1988) · Make It Smart
Back to all articles
Sahawatthanakit (1988) Engineering Team9 min read

R-22 → R-32 / R-454B Chiller Conversion Playbook — Get Ready Before Thailand's 2030 Phase-out

Practical guide to converting R-22 (HCFC) industrial chillers to R-32 / R-454B (HFO) ahead of the Kigali Amendment + DIW Thailand 2030 phase-out — costs, which machines can be converted, TXV/EXV comparison table, and A2L safety requirements.

RefrigerantR-22R-32R-454BPhase-outChillerKigali AmendmentThailand 2030
Roadmap for converting R-22 to R-32 / R-454B on industrial chillers in Thailand
สรุป (TL;DR)

Thailand bans R-22 imports in 2030 — old chillers face 1 of 3 choices: (1) full system swap to R-454B (best, 15+ year life) (2) drop-in R-417a (fastest, but EER drops 8-15%) (3) keep running on reclaimed R-22 (new rules require licensed reclaimers) — start planning before Q4-2027.

Thailand is scheduled to phase out R-22 (HCFC-22) under its Kigali Amendment commitments by 2030 — no new R-22 imports, no use in new equipment, and existing systems limited to reclaimed refrigerant (recovered from decommissioned systems) only. Factories still running R-22 chillers — Carrier 30HXC, Trane RTHB, York YCAS, Daikin McQuay units from the 1990s to early 2000s — need to plan their conversion by Q4-2027 so it lands in the next budget cycle and ahead of the technician shortage.

This article is a practical playbook for Facility / Engineering / Procurement teams who have to decide:

  1. Which R-22 systems are worth converting vs. which to scrap
  2. Which replacement refrigerant to choose — R-32 / R-454B / R-417a / R-407c
  3. Real costs + timeline + risk
  4. The A2L safety provisions you need to prepare for

Thailand Phase-out Timeline — the real numbers

Year R-22 status in Thailand
2013-2024 Import quota restricted (cut 10-15% per year per the DIW plan)
2025-2026 Quota down to ~25% of 2013 — R-22 spot price up 40-60%
2027-2029 Quota down to ~10% — emphasis on reclaim from decommissioned systems
2030 onwards No new R-22 imports; only reclaimed material through a licensed reclaimer (DIW วอ.) is permitted

Note: R-22 still inside a system at 2030 may continue in service — but top-ups + repairs must use reclaimed refrigerant only. Reclaimed price is projected at ≥ ฿15,000/kg by 2030 (vs ฿2,800-3,500/kg in 2026).

Retrofit candidate comparison for R-22 chillers

Replacement ASHRAE Safety GWP Glide EER vs R-22 Compressor swap? Oil change Cost per ton-R Best for
R-32 A2L (mildly flammable) 675 0°C +5% to +8% New required (A2L compressor + control) New POE ฿8,000-12,000 New equipment only — not a retrofit
R-454B (HFO blend) A2L 466 <1°C -2% to +3% New required (A2L compressor) New POE ฿9,000-14,000 New chiller + capital upgrade
R-417a A1 2,346 4°C -8% to -15% Reuse existing Mineral → POE ฿3,500-5,500 Quick drop-in retrofit — old systems with <5 years left
R-407c A1 1,774 7°C -3% to -8% TXV swap required (high glide) Mineral → POE ฿5,500-7,500 Mid-tier retrofit — average systems
R-422a / R-422d A1 3,143 / 2,729 5°C -5% to -10% Reuse existing Mineral OK ฿4,500-6,500 Drop-in for supermarket / cold storage

GWP warning: R-417a + the R-422 series carry high GWP (>2,000) → may need replacing again by 2035 (the Kigali HFC phase-down step) — use only to extend the life of a chiller you plan to decommission within 5-8 years.

3-option decision tree

Option 1 — Full system replacement (new R-454B / R-32)

Choose if: chiller is <8 years old + system still sound + a 15-25 year investment horizon = R-22 → R-454B with new compressor + new EXV + new POE oil. Same or higher cooling capacity.

  • Cost: ฿35,000-55,000 per ton-refrigeration (TR) for a 100-500 TR chiller
  • Timeline: design + spec + install, 3-5 months
  • EER gain: +5-15% (depending on heat exchanger refurb)
  • New service life: 15-20 years
  • Standard: ASHRAE 15 A2L compliance — machine-room ventilation + leak detector per EN 378

Option 2 — Drop-in retrofit (R-417a)

Choose if: chiller is 10-15 years old + budget is tight + you need 3-5 more years of life

  • Cost: ฿8,000-15,000 per TR (refrigerant + flush + POE oil + filter drier)
  • Timeline: 1-2 weeks (including recovery + recharge)
  • EER loss: -8% to -15% → higher power bill
  • New service life: 3-7 years
  • Standard: ASHRAE 34 A1 — no change to the safety system

Option 3 — Continue on reclaimed R-22

Choose if: chiller has <5 years left + the system has no leak

  • Cost: ฿0 capex — but top-ups require reclaimed R-22 from a DIW-licensed reclaimer
  • 2026 price: ฿3,500-5,000/kg
  • 2030 price: ฿15,000+/kg (projected)
  • Risk: a major leak in 2028+ → there may be no R-22 to buy → chiller down → emergency replacement at 1.5x the cost

A2L safety — what R-22 never required

R-32 and R-454B are classified A2L (mildly flammable) under ASHRAE 34 — low flammability, but they require extra provisions:

  1. Machine-room ventilation: flow rate ≥ 0.0875 × √(M) cfm per kg of refrigerant charge (ASHRAE 15-2022 §7.4.2)
  2. Refrigerant leak detector per EN 378: temperature + concentration sensors — alarm setpoint at 25% LFL
  3. Electrical equipment in the machine room: ATEX Zone 2 or NEC Class I Div 2 where concentration risk exists
  4. Charge limit: R-32 max 1.84 kg per occupied space (IEC 60335-2-40)
  5. Refrigerant tech PPE: face shield + flame-resistant gloves + EN 1149 antistatic clothing

Extra cost: upgrading a machine room to A2L = ฿150,000-450,000 per chiller room depending on size.

Selection guide by chiller type

Chiller Type OEM-recommended R-22 replacement Note
Air-cooled screw chiller (Carrier 30HXC / Trane RTHB) R-454B (new) or R-417a (drop-in) New = best EER; drop-in = life extension
Water-cooled centrifugal (Trane CenTraVac / York YT) R-513A (old R-134a → low-GWP) R-22 centrifugals are rare — usually R-134a/R-123
Reciprocating chiller (Carrier 30RH / York YCAS) R-407c or R-422a Old technology — often scrapped instead
Rooftop unit (RTU) — light commercial R-32 (new unit) DX coil — full unit replacement

Related services

SAHA supplies and advises on:

  • Replacement refrigerants: R-454B, R-417a, R-407c, R-422a — AHRI 700:2019 certified every lot
  • POE compressor oil: Emkarate™ RL series — viscosity per the chiller OEM spec
  • Refrigerant recovery service: recovery machine + cylinders + full DIW (วอ.) license
  • A2L safety upgrade consult: ventilation + leak detector + ATEX equipment supply
  • Bulk refrigerant cylinders: 11.3 kg disposable, 48 kg refillable, 750 kg bulk container

Summary for procurement + facility managers

Recommended sequence:

  1. Q3-Q4 2026: Audit all R-22 chillers — record age / capacity / leak history / R-22 charge
  2. Q1 2027: Rank chillers against the decision tree (replace / retrofit / continue)
  3. Q2-Q3 2027: Spec + tender — issue a TOR that requires ASHRAE 15 A2L compliance for replacements
  4. Q4 2027 - Q4 2028: Install the first batch (high-priority chillers)
  5. 2029: Close out R-22 cylinder inventory — switch to reclaimed stock
  6. 2030: Remaining R-22 machines → planned decommissioning

Don't wait until Q1 2030 to start — Thailand has a severe shortage of R-454B installers and A2L-trained techs, and installation prices will spike after 2028.


This article summarizes the regulatory framework and technical options — it is not model-specific advice. For converting a particular chiller model, contact the Sahawatthanakit (1988) engineering team for a site survey + system selection report with ROI calculation.

Share:LINEFacebook
Free download · no sales call

Get this guide as a reference brief (PDF)

Summary + full section list + standards cited, Saha-branded for your memo/RFQ — emailed to you too.

Your email is used only to send the brief + contact from the Saha team · never shared.

Free consult · a prompt, real quote during business hours

Questions after reading? Talk to our engineers

Tell us what you need — our engineers help you spec it right, with a real quote. No charge.

Or reach us directly:02-096-2118LINE: @sahawatt1988
Related Services

Need help with this in your facility?

Our team handles full procurement and installation for the topics covered in this article. Free quote promptly during business hours.

Another line of ours — spreadsheet tools for SMEs

Landed Cost Per Unit — Import Costing (Thai + English editions)

Know what one unit really costs once it reaches your warehouse — duty, VAT, clearance and trucking included, with the lowest price that still meets your target margin.

Compare — buying decision

Comparison tables related to this article

Related content

Article

VRF/VRV vs Chilled-Water Chiller: Choosing Factory/Office/Cleanroom HVAC — Load, Efficiency, and EN 378 Refrigerant-Charge Limits for Thailand

Industrial HVAC buyer's guide: compare VRF/VRV (refrigerant-to-room) vs chilled-water chiller (AHU/FCU) → calculate cooling load → IEER/IPLV efficiency → R-32 A2L charge limits per EN 378 / ISO 5149 → contractor checklist + cleanroom considerations + Thai ambient +38°C de-rating for factories and offices.

Read
Article·12 min

Pick the Right Refrigerant for the Job — A Contractor's Field Guide: Charge Tables by System (Split / VRF / Chiller / Cold Room / Ice Plant / Auto) + R-22/R-404A Replacements + How to Source Cylinders Fast

Field guide for HVAC/R contractors in Thailand: choose the correct refrigerant by actual system type (residential/commercial Split & VRF, chillers, MT/LT cold rooms, ice plants, automotive, ULT) + R-22/R-404A drop-in & retrofit table + compressor oil you must change with it (MO/POE) + how to source refrigerant fast at contractor/fleet pricing.

Read
Article

Natural Refrigerant in Thailand 2026 — R-290 / R-600a / R-744 Selection Guide

Natural refrigerant selection for commercial + industrial Thailand — R-290 propane, R-600a isobutane, R-744 CO2. Kigali Amendment compliance + A3 safety class + capex/OPEX comparison + Thai regulatory + supplier landscape

Read
Article·8 min

Thailand's Air Conditioner Export Boom 2026 — How to Choose the Right Refrigerant Grade Under the Law

Thailand is a top global air-conditioner exporter and 2026 shipments are surging on the European heatwave. This article covers the export figures, why refrigerant demand is climbing, and how to choose R-32 / R-410A / R-454B correctly under the Kigali Amendment and EU F-gas rules — for technicians and factories.

Read