Sahawatthanakit (1988) Co., Ltd.
SAHAWATTHANAKIT(1988) · Make It Smart
Back to all articles
6 min read

POE vs Mineral Oil — Do You Have to Change the Compressor Oil When Moving from R22 to an HFC Refrigerant?

How POE oil differs from mineral oil, and whether the compressor oil must change when an R22 system moves to R407C or another HFC. Residual mineral oil, retrofit routes and a checklist — from Lubrizol and Emkarate documents.

POE vs mineral oilR22 retrofit oil changeR22 to R407C retrofitmineral oil not miscible with HFCpolyol esterEmkarate RLresidual mineral oil retrofit
Technician charging refrigerant from a cylinder through a manifold gauge set during a refrigerant and oil changeover

Photo by Bulat843 / Pexels

สรุป (TL;DR)

How POE oil differs from mineral oil, and whether the compressor oil must change when an R22 system moves to R407C or another HFC. Residual mineral oil, retrofit routes and a checklist — from Lubrizol and Emkarate documents.

The short answer

  • If the system moves to an HFC refrigerant (for example R407C), the oil must become POE, and as much of the old mineral oil as possible must be removed, because mineral oil does not mix with HFC.
  • Residual mineral oil can reach about 10% of the charge, according to the Emkarate RL brochure, and can spoil the miscibility of the POE — leading to fouling of the evaporator and falling efficiency.
  • Moving to R32 or R410A is more than an oil change — it normally means equipment or a compressor designed for that refrigerant. See our R22 and retrofit guidance.
  • Follow the compressor maker for oil type and grade — see how to choose a POE grade.

How POE and mineral oil differ

Topic Mineral oil POE (polyol ester)
Miscibility with HFC Not miscible Designed to mix with HFC
Where it is used Traditional R22 systems (Danfoss's table lists mineral oil for some R22 compressor series) HFC systems, and some R22 compressors
Oil return With HFC, oil collects in the evaporator Oil circulates with the refrigerant and returns to the compressor
Properties — The Emkarate RL brochure states better viscosity index, flash/fire point and pour point than conventional mineral oil

Lubrizol explains that when oil and refrigerant do not mix well, oil accumulates in the evaporator, starving the compressor of lubrication and lowering system efficiency.


Changing from R22 — route by route

Moving to Oil Note
R407C (retrofit) Must become POE A retrofit route that keeps the compressor, but the oil must change and equipment be adjusted per the manufacturer's documents
R32 / R410A The oil the new equipment's maker specifies (per manufacturer tables, often POE or a model-specific ester) Usually a replacement of the machine or compressor, not a recharge of the old unit
R134a and other HFCs POE For systems designed for that refrigerant

A general summary — confirm the route for each machine with its manufacturer.


Residual mineral oil — why retrofits fail

The Emkarate RL brochure explains that even after the mineral oil is drained and a POE is charged, residual mineral oil can make up as much as 10% of the lubricant charge. It can spoil miscibility, coat the evaporator and cut efficiency to an unacceptable level. The maker therefore advises removing as much mineral oil as possible, following the oil maker's retrofit procedure.

Our refrigerant retrofit page quotes the criteria compressor makers use — do not skip steps: that page notes that systems failing after a retrofit usually do so because steps were skipped, not because the replacement refrigerant cannot be used.


Checklist before changing oil and refrigerant

  1. Identify the old and the new refrigerant, and confirm the machine's manufacturer allows the route.
  2. Check the oil grade the compressor maker specifies — see the Emkarate RL grade table by compressor type.
  3. Plan the removal of the old mineral oil following the oil maker's and compressor maker's procedures.
  4. Replace the parts the manufacturer's documents require, such as the filter-drier, and check pressure-relief devices.
  5. Keep the oil container closed until you are ready to charge — compressor makers set a very low water content for the oil.

FAQ

Can POE be mixed with mineral oil? Not recommended — a large residue of mineral oil spoils the miscibility of POE with the refrigerant, so as much as possible must be removed in a retrofit.

Can I charge R32 into an old R22 unit? No — R32 and R22 work at different pressures and with different oils; use equipment designed for R32. See our R22 and R32 pages.

Can Emkarate RL be used for the oil change in a retrofit? The maker states Emkarate RL supports changeovers from CFC and HCFC to HFC systems and is designed for both initial fill and service fill — but the grade must match what the compressor maker specifies.


Ask for advice and a quotation

Planning a retrofit or an oil change? Send the compressor model, the old refrigerant and the new one, and we check the oil grade and quote — see Emkarate RL POE compressor oil. Prices follow grade, size and volume, so none is published on the website.

Share:LINEFacebook
Free download · no sales call

Get this guide as a reference brief (PDF)

Summary + full section list + standards cited, Saha-branded for your memo/RFQ — emailed to you too.

Your email is used only to send the brief + contact from the Saha team · never shared.

Free consult · a prompt, real quote during business hours

Questions after reading? Talk to our engineers

Tell us what you need — our engineers help you spec it right, with a real quote. No charge.

Or reach us directly:02-096-2118LINE: @sahawatt1988
Related Services

Need help with this in your facility?

Our team handles full procurement and installation for the topics covered in this article. Free quote promptly during business hours.

Another line of ours — spreadsheet tools for SMEs

Landed Cost Per Unit — Import Costing (Thai + English editions)

Know what one unit really costs once it reaches your warehouse — duty, VAT, clearance and trucking included, with the lowest price that still meets your target margin.

Compare — buying decision

Comparison tables related to this article

Related content

Article·7 min

Which Compressor Oil Does an Air-Conditioner Use? Choosing POE for HFC Systems and Compressor Types (Emkarate RL22H–RL220H Table)

Which compressor oil does an air-conditioner or cold room use? How to choose POE oil by HFC refrigerant and compressor type, with the Emkarate RL22H–RL220H grade table, viscosity values and an R32 caution — from the makers' documents.

Read
Article·8 min

Thailand's Air Conditioner Export Boom 2026 — How to Choose the Right Refrigerant Grade Under the Law

Thailand is a top global air-conditioner exporter and 2026 shipments are surging on the European heatwave. This article covers the export figures, why refrigerant demand is climbing, and how to choose R-32 / R-410A / R-454B correctly under the Kigali Amendment and EU F-gas rules — for technicians and factories.

Read
Article

R417a, R454C, R123 — Made-to-Order Refrigerants for R-22 Retrofit, Low-GWP Chillers, and Centrifugal Chillers

A guide to three hard-to-source refrigerant grades in Thailand — R417a (drop-in R-22 replacement, no compressor change), R454C (very low-GWP A2L for new equipment), R123 (low-pressure centrifugal chiller, R-11 replacement) — with when to use each.

Read
Article·16 min

Food & Beverage and Cold-Chain Factory Fit-Out and Maintenance Field Guide — Select Refrigeration/Refrigerants to ASHRAE 15/EN 378/ISO 5149 · Hot-Washdown PU-Cement Floors · Food/Pharma Corrosion Coatings · Boiler-Cooling-RO Water · ISO 8573 Food-Contact Air + How to Lock In Material Pricing

Field guide for food & beverage and cold-storage plant owners and engineering/maintenance teams: plan the whole factory with food safety governing every choice — select the refrigeration system/refrigerant by temperature band and refrigerant safety per ASHRAE 15/EN 378/ISO 5149, handle ultra-low/freeze-dry and retrofit of legacy R-13B1, lay PU-cement floors that survive hot-water washdown and food acids in wet zones, coat walls/tanks to food/pharma grade, control process water (boiler/cooling/RO/CIP) and cooling-tower legionella, and control food-contact compressed-air quality to ISO 8573 — plus how to standardize materials to lock pricing and delivery for the whole plant.

Read